Smoke and fire curtains

 

High performance fire containment curtain

Our comprehensive range ensures suitability for your building fire safety regulation requirements, enabling localised, fire compartments to be formed to limit the spread of fire throughout properties. 

 

COntact us

Fire Curtain - FC8

Fire Curtain with up to 3-hour Fire Resistance

High-performance fire containment curtains engineered to meet exacting British Standards. FC8 fire curtains are manufactured from woven glass fibre, offering fire resistance at temperatures up to 1000°C for as long as 180 minutes. Built to endure the most demanding fire conditions, FC8 curtains deliver exceptional protection for both people and property. Integrated stainless steel wire reinforcement improves structural integrity and shape retention during deployment, ensuring reliable compartmentation and helping to prevent the spread of fire throughout a building. These fire compartmentation curtains are specified in commercial, industrial, and public buildings, helping to control fire spread while maintaining safe, protected escape routes when it matters most.

Product Specifications

Features & Benefits

Offering up to 180-minutes fire resistance, our FC8 fire curtains feature a number of enhanced features to optimise and enhance your building’s fire safety systems and procedures.

  1.  Headbox - 1.2mm galvanized mild steel with 2mm end caps.

     

  2. Rollers - 76mm coated mild steel tube.

     

  3. Motors - 24V DC.

     

  4. Fabric - C41000WK.

     

  5. Bottom Bar - 20mm x 40mm mild steel twin angle.

     

  6. Side Guides - 100 x 50 rolled steel with 50 x 60 C-Channel.

     

  7. Electronics - See separate spec sheet.

     

  8. Warranty - A manufacturer’s warranty is provided for a period of one year. Exclusions may apply if any element is sublet to an unauthorised party.
Sizing

Maximum Dimensions

Model

Maximum Width (m)

Maximum Drop (m)

Single Roller

5.5

8

Multi Roller

Unlimted

8

Headbox Sizes & Features

The size of the curtain roller housing (headbox) depends on the fire curtain’s drop and width requirements. Our range of standard headbox sizes for FC8 fire curtains, designed to integrate with, and seamlessly enhance, your building’s fire safety systems:

  • Type A (Single Roller Headbox): The standard headbox for use with curtain widths up to 5.5m, supporting up to 8m curtain drop.
  • Type C (Over Under Headbox): The standard headbox, supporting unlimited curtain widths with up to 8m curtain drop.
Compliance & Standard

Compliance & Standard

The FC8 fire curtains are tested and approved to exacting British standards. FC8 offers a versatile, high-performance fire containment solution for UK industrial, commercial, residential and public buildings, protecting property and occupants in the event of emergencies. The fire curtains are approved to the following standards to ensure maximum safety and operational reassurance:

Machine Directive - 2006/42/EC

EMC Directive - 2014/30/EU

BS 8524-1 - Active fire curtain barrier assemblies – specification.

BSEN 1634-1 - Fire resistance test for door and shutter assemblies and openable windows.